The DirectAire Al is an all aluminum lightweight directional airflow panel that uses patent pending technology to angle the air toward the equipment achieving a 93% Capture Index. This means that 93% of the airflow delivered through the airflow panel is entering the face of the server rack, providing the highest cooling capacity and energy efficiency of any aluminum airflow panel on the market. 

Directional airflow panels maximize the financial performance of any new or existing data center. The precise delivery of air reduces bypass airflow allowing new facilities to reduce the number of CRAH units. Retrofits can set CRAH units with fixed speed fans to standby mode or adjust variable fan drives to operate at a lower static pressure, saving energy. Likewise the 93% Capture Index eliminates the need for a full containment system. The facilities overall cooling capacity will also be improved allowing for the addition of IT equipment without the capital investments on infrastructure.

Airflow Performance Information

DirectAire® Al
 Pressure (in. H2O) CFM (w/o Damper) kW/Rack (93% CI)
0.02 1123 8.3
0.04 1572 11.6
0.05 1751 12.9
0.06 1913 14.1
0.08 2200 16.2
0.10 2451 18.1
0.12 2678 19.8
0.14 2886 21.3
0.16 3079 22.7
0.18 3260 24.1
0.20 3430 25.3

*Cooling capacities were calculated using the following formula:(CFM x Capture Index %) / 126(CFM needed to cool 1kW @ 25ºF ΔT)= kW per rack.